Technical Guide · Package Substations

    What Is a Package Substation and How Does It Work?

    A component-by-component technical breakdown of package and unit substations, their power flow, types, IEC compliance requirements, and industrial applications across Saudi Arabia.

    EAMFCO Package Substations

    Factory-assembled and fully tested package substations integrating RMU, transformer, and LV panel IEC-compliant and configured for Saudi industrial, oil & gas, and infrastructure projects.

    Need a substation specification?

    Our engineers provide load calculations, voltage level selection, and full documentation for Saudi project tenders.

    Definition

    A package substation is a factory-assembled, fully tested electrical installation that integrates medium voltage (MV) switchgear, a power transformer, and a low voltage (LV) distribution panel within a single compact enclosure. It converts incoming MV supply (typically 13.8 kV or 33 kV in Saudi Arabia) to utilisation voltage (380/400 V), ready for direct connection to a facility's LV distribution network.

    Main Components of a Package Substation

    1. Medium Voltage (MV) Switchgear Ring Main Unit (RMU)

    The Ring Main Unit is the MV interface between the incoming SEC or project supply network and the transformer. It provides switching, isolation, and protection functions at the medium voltage level. In package substations supplied to Saudi projects, the RMU is typically SF₆-insulated (sealed-for-life) with rated voltages of 12 kV, 17.5 kV, or 36 kV depending on the incoming supply.

    A standard RMU configuration for a loop-fed SEC network is 2L+T (two load-break switches for the incoming and outgoing ring cables, plus one fused or circuit-breaker-protected transformer feeder). More complex configurations 3L+T, 4L+T are used where multiple ring feeds or transformer feeders are required.

    2. Power Transformer

    The transformer steps down the MV voltage to the LV utilisation level. Package substations in Saudi Arabia use either:

    Transformer TypeCooling MethodTypical ApplicationAdvantage
    Oil-immersed (ONAN/ONAF)Oil natural / forced airOutdoor industrial, infrastructureLower cost, well-proven, easier repair
    Dry-type (AN/AF)Air natural / forced airIndoor installations, buildingsNo fire risk, no oil containment required
    Cast resin (AN/AF)Air natural / forced airHarsh environments, offshore, minesHighest moisture and contamination resistance

    Standard ratings for Saudi project package substations range from 250 kVA to 2,500 kVA. Larger ratings (up to 5,000 kVA) are available in skid-mounted and containerised formats. Transformer vector groups are typically Dyn11 for distribution and YNyn0 for special applications as specified by SEC or project requirements.

    3. Low Voltage (LV) Distribution Panel

    The LV panel receives the transformer secondary output and distributes it to the facility's outgoing feeders. In a package substation, the LV panel is factory-wired and tested as part of the complete assembly. It typically includes:

    • Incomer circuit breaker (ACB or MCCB) with metering kWh, kVAR, power factor, demand
    • Outgoing feeder MCCBs or ACBs rated for individual distribution circuits
    • Busbar assembly rated from 630A to 4,000A depending on transformer rating
    • Neutral and earth busbars with appropriate sizing
    • Current transformers (CTs) for metering and protection
    • Capacitor bank terminals for future APFC panel connection (where specified)

    4. Protection Systems

    Package substations incorporate layered protection to meet IEC and SEC requirements:

    Protection FunctionLocationDevice
    MV overcurrent & earth faultRMU transformer feederHRC fuses or relay-controlled VCB
    Transformer overtemperatureTransformer bodyWinding temperature indicator (WTI/OTI)
    Buchholz relay (oil transformers)Transformer conservator pipeGas and surge detection relay
    LV overcurrentLV panel incomerACB/MCCB with trip unit
    LV earth faultLV panel incomerResidual current relay or ELCB
    Transformer overpressure (oil type)Transformer tankPressure relief device

    Power Flow Through a Package Substation Step by Step

    1

    MV Incoming Supply

    The SEC or project MV network delivers power at 13.8 kV, 33 kV, or other designated voltage via underground cable or overhead line to the RMU incoming terminals.
    2

    RMU Switching and Protection

    The RMU load-break switch connects the incoming ring cable to the substation busbar. The transformer feeder switch (or fused switch) isolates and protects the transformer from MV faults. The outgoing ring switch connects the continuing loop to the next substation.
    3

    MV/LV Transformation

    The transformer primary winding receives MV voltage from the RMU. The magnetic core steps down the voltage to the rated LV secondary typically 400V three-phase at 50 Hz for Saudi distribution systems. Transformation losses (typically 0.5–1.5% of rated kVA) appear as heat, dissipated by the cooling system.
    4

    LV Panel Distribution

    The transformer secondary connects via busduct or cable to the LV panel incomer. The incomer breaker provides fault protection and metering. Outgoing feeders distribute power to sub-distribution boards, motor control centres, or directly to large loads across the facility.
    5

    Earthing and Bonding

    The substation enclosure, transformer tank, neutral point, and LV panel earth bar are all bonded to the facility earth grid. TN-S or TN-C-S earthing systems are used in Saudi projects in accordance with IEC 60364 and SEC technical requirements.

    Indoor vs Outdoor Package Substations

    ParameterIndoor (Walk-In / Kiosk)Outdoor (Pad-Mounted / Containerised)
    EnclosureSteel or GRP kiosk, IP33–IP54Weatherproof steel/GRP, IP54–IP65
    VentilationNatural or forced louvred panelsForced ventilation with filters rated for dusty environments
    Climate controlOptional air conditioningThermostat-controlled forced ventilation or A/C
    AccessWalk-in or hinged door panelsSide or end-access doors with padlocking
    InstallationOn concrete pad or raised plinthDirect ground mounting on prepared pad
    Saudi suitabilitySuitable for temperate zonesRequired in outdoor industrial and remote sites
    Typical Saudi useInside industrial buildings, commercial basementsNEOM sites, water plants, oil & gas remote locations

    In Saudi Arabia's outdoor industrial and infrastructure environments where summer ambient temperatures routinely exceed 45°C and windborne sand causes rapid filter clogging outdoor package substations must be specified with Class E2 environmental protection (IEC 62271-202) as a minimum, with forced ventilation systems incorporating sand filters and high-temperature-rated components throughout.

    Compliance: IEC Standards and SEC Requirements

    Package substations supplied to Saudi projects must comply with the following standards as a minimum:

    StandardScope
    IEC 62271-202Primary requirement for factory-built package substations (High-voltage/low-voltage prefabricated substations)
    IEC 62271-200AC metal-enclosed switchgear and controlgear (MV switchboard within substation)
    IEC 60076Power transformers general requirements, temperature rise, losses
    IEC 61439-1 / -2Low voltage switchgear and controlgear assemblies (the LV panel)
    IEC 60529IP degree of protection enclosure classification
    SEC Distribution StandardsSaudi Electric Company technical requirements for substations connected to the SEC MV network specifies RMU configuration, metering, protection settings, and earthing systems
    SASOSaudi Standards, Metrology and Quality Organization mandatory product certification for equipment supplied within the Kingdom

    Where Package Substations Are Used in Saudi Arabia

    Industrial Zones (Jubail, Yanbu, Ras Al Khair)

    Large manufacturing, petrochemical, and fabrication facilities require multiple package substations to step down from the SEC 13.8 kV or 33 kV ring network to utilisation voltage for motors, welding, and process loads.

    Oil & Gas Infrastructure

    Remote pump stations, pipelines, and compressor stations use containerised or skid-mounted package substations where conventional civil substation construction is impractical and delivery speed is critical.

    Water and Desalination Plants

    NWC-operated pump stations and SWCC desalination facilities throughout the Kingdom use package substations for distributed MV-to-LV transformation, with multiple substations serving different process areas.

    Commercial Developments

    High-rise buildings, shopping malls, and mixed-use developments in Riyadh, Jeddah, and Dammam use indoor kiosk-type package substations in electrical rooms to serve tenant and common area loads.

    Giga-Projects (NEOM, Diriyah, Red Sea)

    Vision 2030 infrastructure projects require rapid deployment of electrical infrastructure. Containerised package substations are used extensively at construction phase to power temporary camps, manufacturing facilities, and permanent infrastructure.

    Universities and Government Facilities

    Campus-style facilities such as KFUPM use package substations to distribute power from a central MV ring to individual buildings eliminating the need for a dedicated transformer room in each building.

    Frequently Asked Questions

    Q: What is the difference between a package substation and a unit substation?

    A: A package substation integrates three components in one factory-assembled enclosure: an MV Ring Main Unit (RMU), a transformer, and an LV distribution panel. A unit substation contains only a transformer and LV panel it connects to a separately installed MV switchgear. Package substations are self-contained and require no external MV connections beyond the incoming cable.

    Q: What voltage levels are used in package substations in Saudi Arabia?

    A: The most common MV incoming voltages for SEC-connected package substations in Saudi Arabia are 13.8 kV and 33 kV, with 11 kV in some legacy systems. LV output is typically 380/400V three-phase at 50 Hz. Standard transformer ratings range from 250 kVA to 2,500 kVA, with larger ratings available in skid or containerised formats.

    Q: Are EAMFCO package substations factory tested before delivery?

    A: Yes. All EAMFCO package and unit substations are factory assembled and tested before shipment, including high-voltage dielectric tests on MV switchgear, insulation resistance testing on all interconnecting wiring, functional testing of protection relays, and verification of interlocks. A factory acceptance test (FAT) report is provided with each unit.

    Q: How long does it take to install a package substation?

    A: Because all components are pre-assembled and tested at the factory, on-site installation is significantly faster than a conventional substation. A single compact package substation can typically be placed, cabled, and energised within 1 to 3 days. Multiple unit installations on large projects may require phased energisation over 1 to 2 weeks.

    EAMFCO - Factory-Assembled Package Substations for Saudi Arabia

    EAMFCO manufactures package and unit substations integrating SF₆ RMUs, oil and dry-type transformers, and IEC 61439-compliant LV panels factory assembled, tested, and documented for Saudi industrial, oil & gas, and infrastructure projects. Continue reading:

    ABOUT COMPANY

    EAMFCO LogoEAMFCO
    Saudi Made Logo

    CONTACT INFO

    You can always contact us via email or phone. Get in touch with contact and get a quote form.

    Second Industrial City, Dammam, Saudi Arabia
    920010487
    info@eamfco.com

    COMPANY SUPPORT

    KSA Map

    Our support team is available during business hours.

    Sunday-Thursday: 7am to 5pm
    Friday & Saturday: Closed

    We deliver across the Kingdom.